Standard intelligent fire detectors are advanced in design, improved in performance and has unique features that benefit the installer and the end user.
The range includes ionisation and optical smoke detectors, heat detectors as well as dual-state detection that provides maximum protection and minimum false alarms. The Fire Alarm system can be configured to reduce the smoke detection element providing heat detection at preset times when routine processes could cause false alarms. Outside of these times, both elements are enabled providing enhanced Fire Detection.
All have an unobtrusive profile, a zero insertion force base, user- friendly addressing and extended data and alarm features. A manual call point, an isolating base, sounders, beacons and other compatible products are also available.
These detectors have been carefully researched and the range has undergone rigorous testing to ensure that it meets British standards but also the demands of today’s high technology environments.
KeyCall® is a revolutionary patent-granted Key Operated Fire Alarm Activation Device which has been developed specifically for ‘approved’ applications where standard fire alarm call points would be vulnerable to abuse. Developed by Fixfire® in response to growing demand from the Mental Health Care sector, KeyCall® is a revolutionary one-piece analogue addressable key operated manual call point.
Compatible with a wide range of Conventional and Addressable Fire Alarm Systems.
KeyCall® accepts a Euro-Profile style cylinder
Typically suited/keyed-alike cylinders are fitted so that authorised persons can activate KeyCall® using their standard door key.
Key ‘Click-latch’ mechanism ensures key ‘latches’ in correct position to activate Fire Alarm System.
Anti-ligature low-profile flush-mounting design.
Neat minimalistic one piece construction incorporating Fire Alarm interface module.
Red fire indicator illuminates when KeyCall® is activated.
Compatible with a wide range of Conventional and Addressable Fire Alarm Systems
Applications include:
- Prisons
- Mental Healthcare
- Special Educational Needs (SEN) School
British Standard Design requirements...
- Install AFD to voids greater than 800mm
- Treat downward projections exceeding 10% of the void depth as wall
BS5839-Part 1:2013 states:
22.2d) If the system Category is such that automatic fire detection should be provided in any area that contains a horizontal void of 800 mm or more in height, automatic fire detection should also be provided in the void.
22.3j) Ceiling obstructions, such as structural beams, deeper than 10% of the overall ceiling height should be treated as walls [see Figure 10a)]. NOTE 10 Within horizontal voids, beams or obstructions that are deeper than 10% of the overall depth of the void regardless of whether the void is above the ceiling or below the floor, ought to be treated as walls that subdivide the void.
VoidAlert Remote Indicator
Related Downloads
Click a sector to find out more
Standard intelligent fire detectors are advanced in design, improved in performance and has unique features that benefit the installer and the end user.
The range includes ionisation and optical smoke detectors, heat detectors as well as dual-state detection that provides maximum protection and minimum false alarms. The Fire Alarm system can be configured to reduce the smoke detection element providing heat detection at preset times when routine processes could cause false alarms. Outside of these times, both elements are enabled providing enhanced Fire Detection.
All have an unobtrusive profile, a zero insertion force base, user- friendly addressing and extended data and alarm features. A manual call point, an isolating base, sounders, beacons and other compatible products are also available.
These detectors have been carefully researched and the range has undergone rigorous testing to ensure that it meets British standards but also the demands of today’s high technology environments.